The Danfoss LCP 11 is the local control panel for the VLT drive range, Danfoss code number 132B0100. It is a numerical LCP with a four digit display, the standard keypad and no potentiometer, so the reference comes from the terminals, the fieldbus or the up and down keys.
The VLT Micro Drive FC 51 is shipped without a control panel, which keeps the drive itself cheap. You need an LCP to set parameters at the drive, to read the actual frequency, current and fault codes, and to copy a set of settings from one drive to the next. On a line of identical machines one panel is often bought for the whole line and moved between drives, which is why this part is ordered on its own so often.
The panel clips onto the front of the drive and can be removed while the drive is running. With a remote mounting kit it can also be fitted in the door of the control cabinet so the operator can start, stop and set the speed without opening it.
Choose the LCP 11 when the speed reference comes from the PLC, a signal on the terminals or fixed parameters, and the panel is only needed for setting up and for diagnostics.
| Brand | Danfoss |
|---|---|
| Danfoss code number | 132B0100 |
| Type | LCP 11 |
| Product type | Local control panel for VLT drives |
| Description | Numerical local control panel without potentiometer |
| Display | Numerical, 4 digit LED |
| Potentiometer | No |
| Fits | VLT Micro Drive FC 51, and other VLT drives that accept the LCP 11 and LCP 12 |
| Mounting | Clips onto the front of the drive, or panel mounted with a remote mounting kit |
| Function | Local start and stop, speed reference, parameter setting, copy settings between drives |
Where the LCP 11 Is Used
The LCP 11 is the operator interface for the VLT Micro Drive FC 51. Because the drive is shipped without a control panel, this accessory is what allows an engineer to commission the drive at the machine, read the actual motor current and frequency, and copy a proven parameter set from one drive to the next unit on the line. It is used on conveyor drives, pump skids, fan sections, mixers and packaging machines wherever local set-up and local read-out are needed instead of a laptop and MCT 10 software.
- Commissioning a new drive directly at the panel door
- Reading motor frequency, current, power and fault history on site
- Copying parameters from one FC 51 to identical drives (upload and download)
- Local speed adjustment by machine operators (LCP 12, with potentiometer)
- Fault diagnosis and reset without opening a laptop
All VLT Micro Drive FC 51 Models
The full FC 51 range that Renda Trading supplies is listed below. Choose the row that matches your motor rating and supply voltage.
| Code number | Type code | Power | Supply | Current | Size |
|---|---|---|---|---|---|
| 132F0002 | FC-051PK37S2E20H | 0.37 kW | 1 x 200-240 V | 2.2 A | M1 |
| 132F0003 | FC-051PK75S2E20H | 0.75 kW | 1 x 200-240 V | 4.2 A | M1 |
| 132F0005 | FC-051P1K5S2E20H | 1.5 kW | 1 x 200-240 V | 6.8 A | M2 |
| 132F0007 | FC-051P2K2S2E20H | 2.2 kW | 1 x 200-240 V | 9.6 A | M3 |
| 132F0017 | FC-051PK37T4E20H | 0.37 kW | 3 x 380-480 V | 1.2 A | M1 |
| 132F0018 | FC-051PK75T4E20H | 0.75 kW | 3 x 380-480 V | 2.2 A | M1 |
| 132F0020 | FC-051P1K5T4E20H | 1.5 kW | 3 x 380-480 V | 3.7 A | M2 |
| 132F0022 | FC-051P2K2T4E20H | 2.2 kW | 3 x 380-480 V | 5.3 A | M2 |
| 132F0024 | FC-051P3K0T4E20H | 3 kW | 3 x 380-480 V | 7.2 A | M3 |
| 132F0026 | FC-051P4K0T4E20H | 4 kW | 3 x 380-480 V | 9.0 A | M3 |
| 132F0028 | FC-051P5K5T4E20H | 5.5 kW | 3 x 380-480 V | 12.0 A | M3 |
| 132F0030 | FC-051P7K5T4E20H | 7.5 kW | 3 x 380-480 V | 15.5 A | M3 |
| 132F0058 | FC-051P11KT4E20H | 11 kW | 3 x 380-480 V | 23 A | M4 |
| 132F0059 | FC-051P15KT4E20H | 15 kW | 3 x 380-480 V | 31 A | M4 |
| 132F0060 | FC-051P18KT4E20H | 18.5 kW | 3 x 380-480 V | 37 A | M5 |
| 132F0061 | FC-051P22KT4E20H | 22 kW | 3 x 380-480 V | 43 A | M5 |
Control Panels and Accessories
The VLT Micro Drive FC 51 is delivered without a local control panel, so the keypad is ordered as a separate item. Both panels below fit every size in the range.
| Code number | Item | Description |
|---|---|---|
| 132B0100 | LCP 11 | Numerical local control panel without potentiometer |
| 132B0101 | LCP 12 | Numerical local control panel with potentiometer |
Other accessories available on request: IP21 / NEMA Type 1 conversion kit, decoupling plate for EMC-correct cable termination, DIN rail mounting kit for the smaller sizes, braking resistors for units with a brake chopper, and MCT 10 set-up software for PC commissioning.
Frequently Asked Questions
What is Danfoss 132B0100?
Danfoss 132B0100 is the LCP 11 local control panel for the VLT Micro Drive FC 51. It is a numerical operator keypad without a potentiometer, used to set parameters, start and stop the drive, read operating data and reset faults.
Does the VLT Micro Drive FC 51 come with a control panel?
No. The FC 51 drive is supplied without a local control panel. The keypad is ordered separately as LCP 11 or as the alternative LCP version, or the drive can be commissioned from a PC with MCT 10 software.
What is the difference between LCP 11 and LCP 12?
Both are numerical keypads with the same display and menu structure. LCP 12 adds a potentiometer and a hand-mode key so an operator can set the speed directly on the panel. LCP 11 has no potentiometer and is used where the speed reference comes from a signal or from the drive parameters.
Can I copy parameters between drives with LCP 11?
Yes. The panel supports parameter upload from the drive and download to another FC 51, so one commissioned drive can be replicated across identical machines quickly.
Is 132B0100 compatible with all FC 51 power sizes?
Yes. The same panel fits every VLT Micro Drive FC 51 from 0.18 kW to 22 kW, in both single-phase 200-240 V and three-phase 380-480 V versions.
Ordering 132B0100 from Renda Trading
Renda Trading Company supplies Danfoss VLT drives and accessories to industrial customers in Saudi Arabia and the wider Gulf region. Prices are quoted per order because they depend on quantity, delivery time and the rest of the items on your request.
To get a quotation, send us the code number 132B0100 and the quantity you need. If you are not certain that this is the right size, tell us the motor nameplate rating, the supply voltage on site and what the motor drives, and we will confirm the correct model before you order.
- Danfoss code number: 132B0100
- Type code: LCP 11
- Brand: Danfoss
- Family: VLT Micro Drive FC 51