Rated 25 A / 11 kW at 400 V (AC-3), the Siemens 3RT2026-1AC20 is a 3-pole SIRIUS 3RT2 contactor, size S0, operated by a 24 V AC, 50/60 Hz coil. It has 1 NO + 1 NC integrated auxiliary contacts, and Siemens rates it at 40 A for resistive (AC-1) loads at 40 °C. Per the Siemens data sheet the coil picks up within 8 … 40 ms and drops out within 4 … 16 ms.
Contactors in pump, fan, conveyor and compressor panels may switch thousands of times a day, and contact wear is the usual reason for replacement. Keeping a spare of the same order number avoids long stoppages.
See our Siemens industrial controls range, including SIRIUS 3RU2 overload relays and 3RV2 motor starter protectors for the same size.
Technical data
| Siemens order number | 3RT2026-1AC20 |
|---|---|
| Product | SIRIUS 3RT2 power contactor, 3-pole |
| Size | S0 |
| Utilisation category | AC-3 / AC-3e |
| Rated operational current AC-3 at 400 V | 25 A |
| Motor power AC-3 at 400 V | 11 kW |
| Motor power AC-3 at 230 V | 5.5 kW |
| Operational current AC-1 (40 °C, up to 690 V) | 40 A |
| Rated operating voltage, max. | 690 V |
| Coil voltage | 24 V AC, 50/60 Hz |
| Coil operating range | 0.8 … 1.1 x Us (50 Hz) |
| Coil pick-up power (50 Hz) | 81 V·A |
| Coil holding power (50 Hz) | 10.5 V·A |
| Auxiliary contacts (integrated) | 1 NO + 1 NC |
| Closing delay | 8 … 40 ms |
| Opening delay | 4 … 16 ms |
| Mechanical service life, typ. | 10,000,000 operating cycles |
| Power loss per pole (rated current) | 1.9 W |
| Short-circuit protection, main circuit (type 1) | gG: 100 A (690 V, 100 kA), aM: 50 A (690 V, 100 kA), BS88: 100 A (415 V, 80 |
| Ambient temperature (operation) | -25 … +60 °C |
| Connection type | screw-type terminals |
| Mounting | screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715 |
| Dimensions (W x H x D) | 45 x 85 x 97 mm |
| Net weight | 0.39 kg |
| Condition | New, original Siemens |
Typical applications
- Pump, fan and compressor control panels
- Conveyor, mixer and packaging machine drives
- Direct-on-line starters for motors up to 11 kW at 400 V
- Star-delta starter assemblies
Compatibility and replacement
For overload protection mount a SIRIUS 3RU2 thermal overload relay of size S0 directly under the contactor, or combine it with a 3RV2 motor starter protector of the same size using the Siemens link module. The coil voltage is coded in the order number (here 24 V AC, 50/60 Hz), so check it against your control circuit before ordering.
Frequently asked questions
Can I use it for a 7.5 kW motor?
This contactor is rated 11 kW at 400 V (AC-3, 25 A). Choose a contactor whose AC-3 rating at your supply voltage is at least the motor rating.
Which overload relay fits it?
A SIRIUS 3RU2 overload relay of size S0, for example 3RU2126, set to the motor full-load current.
Do you ship to my country, and what is the warranty?
Yes. RendatSP ships worldwide from Yiwu, China, by air in 5 to 7 days once the part is ready, and every part carries a 1-year warranty. Send the order number and quantity on WhatsApp and we will reply with a quotation.
How to order
Message us the order number and quantity. For breakdowns, tell us the delivery address and we will offer the fastest shipping option. If the exact part is discontinued, we confirm the official successor before quoting.
Every part RendatSP supplies is new and original, carries a 1-year warranty and ships worldwide by air in 5 to 7 days once ready (shipping, payment and warranty). Send us the order number and quantity on WhatsApp or through the inquiry form and we will quote the same working day. Agents in Saudi Arabia, Iraq, the UAE, Egypt, Oman, Libya, Morocco, Mauritania, Yemen, Algeria and Jordan.