The Siemens 3RT2015-1AP02 is a SIRIUS 3RT2 power contactor in size S00 that switches three-phase motors up to 3 kW at 400 V (7 A in utilisation category AC-3), with a 230 V AC, 50/60 Hz operating coil. It has 1 NC integrated auxiliary contact, and Siemens rates it at 18 A for resistive (AC-1) loads at 40 °C. At 230 V the AC-3 motor rating is 1.5 kW.
In a direct-on-line or star-delta starter the contactor does the actual switching, while the overload relay or motor starter protector provides protection. A worn contactor shows burnt contacts, humming or chattering, and failure to pull in.
See our Siemens industrial controls range, including SIRIUS 3RU2 overload relays and 3RV2 motor starter protectors for the same size.
Technical data
| Siemens order number | 3RT2015-1AP02 |
|---|---|
| Product | SIRIUS 3RT2 power contactor, 3-pole |
| Size | S00 |
| Utilisation category | AC-3 / AC-3e |
| Rated operational current AC-3 at 400 V | 7 A |
| Motor power AC-3 at 400 V | 3 kW |
| Motor power AC-3 at 230 V | 1.5 kW |
| Operational current AC-1 (40 °C, up to 690 V) | 18 A |
| Rated operating voltage, max. | 690 V |
| Coil voltage | 230 V AC, 50/60 Hz |
| Coil operating range | 0.8 … 1.1 x Us (50 Hz) |
| Coil pick-up power (50 Hz) | 27 V·A |
| Coil holding power (50 Hz) | 4.2 V·A |
| Auxiliary contacts (integrated) | 1 NC |
| Closing delay | 9 … 35 ms |
| Opening delay | 4 … 15 ms |
| Mechanical service life, typ. | 30,000,000 operating cycles |
| Power loss per pole (rated current) | 0.2 W |
| Short-circuit protection, main circuit (type 1) | gG: 35 A (690 V,100 kA), aM: 20 A (690 V,100 kA), BS88: 35 A (415 V,80 kA) |
| Ambient temperature (operation) | -25 … +60 °C |
| Connection type | screw-type terminals |
| Mounting | screw and snap-on mounting onto 35 mm DIN rail according to DIN EN 60715 |
| Dimensions (W x H x D) | 45 x 58 x 73 mm |
| Net weight | 0.217 kg |
| Condition | New, original Siemens |
Typical applications
- Pump, fan and compressor control panels
- Direct-on-line starters for motors up to 3 kW at 400 V
- Switching heaters and resistive loads (AC-1)
- Conveyor, mixer and packaging machine drives
Compatibility and replacement
For overload protection mount a SIRIUS 3RU2 thermal overload relay of size S00 directly under the contactor, or combine it with a 3RV2 motor starter protector of the same size using the Siemens link module. Older 3RT10 contactors were replaced by the 3RT20 series; send us the old order number and we will confirm the current equivalent.
Frequently asked questions
What coil voltage does it need?
Per Siemens: 230 V AC, 50/60 Hz, operating range 0.8 … 1.1 x Us (50 Hz).
How many auxiliary contacts does it have?
It has 1 NC integrated; more can be added with 3RH2911 auxiliary switch blocks.
Do you ship to my country, and what is the warranty?
Yes. RendatSP ships worldwide from Yiwu, China, by air in 5 to 7 days once the part is ready, and every part carries a 1-year warranty. Send the order number and quantity on WhatsApp and we will reply with a quotation.
Ordering tips
Send us the full order number from the label of the old part, or a clear photo of the label, together with the quantity you need. We check the number against the current manufacturer data before we quote and tell you if there is a newer replacement.
RendatSP ships from Yiwu, China, to factories worldwide; air delivery usually takes 5 to 7 days once the part is ready. The part is new and original with a 1-year warranty (shipping, payment and warranty). For a quotation, message us on WhatsApp with the order number and quantity. We also have agents in Saudi Arabia, Iraq, the UAE, Egypt, Oman, Libya, Morocco, Mauritania, Yemen, Algeria and Jordan.