Schneider LC2D12M7 (TeSys D reversing contactors): Reversing Contactor, TeSys Deca, 3P(3NO), AC-3, <=440V 12A, 220V AC 50/60Hz coil, screw clamp terminals.
A reversing contactor assembly combines two LC1D contactors with mechanical interlock and wiring, ready to reverse a three-phase motor.
See our Schneider Electric range.
Technical data
| Schneider reference | LC2D12M7 |
|---|---|
| Product or component type | Reversing contactor |
| Contactor application | Motor control; Resistive load |
| Utilisation category | AC-1; AC-3; AC-3e |
| Device presentation | Preassembled with reversing power busbar |
| Poles description | 3P |
| Pole contact composition | 3 NO |
| [Ue] rated operational voltage | Power circuit: <= 690 V AC 25…400 Hz; Power circuit: <= 300 V DC |
| [Ie] rated operational current | 25 A (at <60 °C) at <= 440 V AC AC-1 for power circuit; 12 A (at <60 °C) at <= 440 V AC AC-3 for power circuit; 12 A (at <60 °C) at <= 440 V AC AC-3e for power circuit |
| Motor power kW | 3 kW at 220…230 V AC 50 Hz; 5.5 kW at 380…400 V AC 50 Hz; 5.5 kW at 415 V AC 50 Hz; 5.5 kW at 440 V AC 50 Hz; 7.5 kW at 500 V AC 50 Hz; 7.5 kW at 660…690 V AC 50 Hz |
| Motor power hp | 1 hp at 115 V AC 60 Hz for 1 phase motors; 2 hp at 230/240 V AC 60 Hz for 1 phase motors; 3 hp at 200/208 V AC 60 Hz for 3 phases motors |
| Control circuit type | AC at 50/60 Hz |
| [Uc] control circuit voltage | 220 V AC 50/60 Hz |
| Auxiliary contact composition | 1 NO + 1 NC |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947 |
| Overvoltage category | III |
| [Ith] conventional free air thermal current | 10 A (at 60 °C) for signalling circuit; 25 A (at 60 °C) for power circuit |
| Irms rated making capacity | 250 A at 440 V for power circuit conforming to IEC 60947; 140 A AC for signalling circuit conforming to IEC 60947-5-1 |
| Rated breaking capacity | 250 A at 440 V for power circuit conforming to IEC 60947 |
| Associated fuse rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1; 40 A gG at <= 690 V coordination type 1 for power circuit |
| Average impedance | 2.5 MOhm – Ith 25 A 50 Hz for power circuit |
| Dimensions (W x H x D) | 90 x 77 x 86 mm |
| Condition | New, original Schneider Electric |
Key characteristics (per Schneider)
- Reversing Contactor
- TeSys Deca
- 3P(3NO)
- AC-3
- <=440V 12A
- 220V AC 50/60Hz coil
- screw clamp terminals
Typical applications
- Conveyors, hoists and doors
- Reversing motor starters
Compatibility and replacement
Check the rating and coil voltage code (M7 = 220 V AC).
Frequently asked questions
Can you help me identify the right replacement?
Yes. Send us a photo of the label of the old part, or its full order number, and we will confirm the exact match or the official successor before quoting.
Can I get a datasheet?
The official manufacturer datasheet is the source of the technical data above; we can send the PDF with the quotation on request.
Is the interlock included?
Yes, the LC2D is a pre-wired reversing assembly with mechanical interlock, as listed by Schneider.
How fast can you deliver, and is there a warranty?
Air shipping usually takes 5 to 7 days once the part is ready, to almost any country. Each part is new and original with a 1-year warranty. Message us on WhatsApp with the order number for a quotation.
Before you order
Compare the complete order number on the old unit with this page, including the suffix: in most ranges the last characters set the coil voltage, current range or version. If the label is worn, send us a photo and we will identify the part.
Need it fast? Send the order number, quantity and delivery country on WhatsApp or through the inquiry form and we reply with a quotation the same working day. All parts are new and original, covered by a 1-year warranty, and ship worldwide by air in 5 to 7 days once ready (shipping, payment and warranty). Local agents: Saudi Arabia, Iraq, the UAE, Egypt, Oman, Libya, Morocco, Mauritania, Yemen, Algeria and Jordan.