The Schneider Electric LC1D25E7 is a TeSys Deca 3-pole contactor rated 25 A in AC-3 at up to 440 V, for motors of 11 kW at 380/400 V, with a 48 V AC 50/60 Hz coil. It carries 1 NO + 1 NC auxiliary contacts as standard. At 220/230 V the AC-3 motor rating is 5.5 kW.
The contactor switches the motor or load on command from the PLC, a push-button or a timer. Burnt or pitted contacts, coil noise and failure to close are the usual signs that it needs to be replaced.
See our Schneider Electric range for TeSys overload relays and GV2 breakers.
Technical data
| Schneider reference | LC1D25E7 |
|---|---|
| Product or component type | Contactor |
| Contactor application | Resistive load; Motor control |
| Utilisation category | AC-3; AC-3e; AC-1; AC-4 |
| Poles description | 3P |
| [Ue] rated operational voltage | Power circuit: <= 690 V AC 25…400 Hz; Power circuit: <= 300 V DC |
| [Ie] rated operational current | 25 A (at <60 °C) at <= 440 V AC AC-3 for power circuit; 40 A (at <60 °C) at <= 440 V AC AC-1 for power circuit; 25 A (at <60 °C) at <= 440 V AC AC-3e for power circuit |
| [Uc] control circuit voltage | 48 V AC 50/60 Hz |
| Motor power kW | 5.5 kW at 220/230 V AC 50/60 Hz (AC-3); 11 kW at 380/400 V AC 50/60 Hz (AC-3); 11 kW at 415/440 V AC 50/60 Hz (AC-3); 15 kW at 500 V AC 50/60 Hz (AC-3) |
| Motor power hp | 3 hp at 230/240 V AC 50/60 Hz for 1 phase motors; 2 hp at 115 V AC 50/60 Hz for 1 phase motors; 7.5 hp at 230/240 V AC 50/60 Hz for 3 phases motors |
| Compatibility code | LC1D |
| Pole contact composition | 3 NO |
| Protective cover | With |
| [Ith] conventional free air thermal current | 10 A (at 60 °C) for signalling circuit; 40 A (at 60 °C) for power circuit |
| Irms rated making capacity | 140 A AC for signalling circuit conforming to IEC 60947-5-1; 250 A DC for signalling circuit conforming to IEC 60947-5-1 |
| Dimensions (W x H x D) | 45 x 85 x 92 mm |
| Condition | New, original Schneider Electric |
At a glance
- Contactor
- TeSys Deca
- 3P(3NO)
- AC-3/3e
- <=440V 25A
- 48V AC coil
- screw clamp terminals
Typical applications
- Star-delta starter assemblies
- Heating and resistive loads (AC-1)
- Motor starters up to 11 kW at 400 V
- Conveyors and packaging machines
Compatibility and replacement
Pairs with the TeSys LRD thermal overload relay (direct mounting) and the GV2 motor circuit breaker. Add-on blocks such as LADN11 (1NO+1NC) or LADN22 (2NO+2NC) fit on the front. LC1D contactors from older TeSys D production are replaced one-to-one by TeSys Deca of the same reference.
Frequently asked questions
Can it switch heaters or resistive loads?
Yes. For AC-1 (resistive) loads Schneider rates it at 40 A.
What is the coil voltage?
48 V AC 50/60 Hz, per the Schneider data sheet.
What motor size can it switch?
Up to 11 kW at 380/400 V in AC-3 (25 A).
Which overload relay fits?
TeSys LRD relays mount directly under the contactor; choose the setting range that covers the motor rated current.
Do you ship to my country, and what is the warranty?
Yes. RendatSP ships worldwide from Yiwu, China, by air in 5 to 7 days once the part is ready, and every part carries a 1-year warranty. Send the order number and quantity on WhatsApp and we will reply with a quotation.
How to order
Message us the order number and quantity. For breakdowns, tell us the delivery address and we will offer the fastest shipping option. If the exact part is discontinued, we confirm the official successor before quoting.
Need it fast? Send the order number, quantity and delivery country on WhatsApp or through the inquiry form and we reply with a quotation the same working day. All parts are new and original, covered by a 1-year warranty, and ship worldwide by air in 5 to 7 days once ready (shipping, payment and warranty). Local agents: Saudi Arabia, Iraq, the UAE, Egypt, Oman, Libya, Morocco, Mauritania, Yemen, Algeria and Jordan.