The Schneider Electric GV3P65 is a TeSys GV3 motor circuit breaker with thermal-magnetic protection, thermal setting 48 … 65 A, magnetic tripping at 910 A.
Set the thermal dial to the motor nameplate current. A breaker that trips at start-up can point to a wrong setting, a mechanical jam or a failing motor.
See our Schneider Electric range.
Technical data
| Schneider reference | GV3P65 |
|---|---|
| Product or component type | Motor circuit breaker |
| Device application | Motor protection |
| Trip unit technology | Thermal-magnetic |
| Poles description | 3P |
| Network type | AC |
| Utilisation category | Category A conforming to IEC 60947-2; AC-3 conforming to IEC 60947-4-1 |
| Network frequency | 50/60 Hz conforming to IEC 60947-2 |
| Motor power kW | 30 kW at 400/415 V AC 50/60 Hz; 45 kW at 500 V AC 50/60 Hz; 55 kW at 690 V AC 50/60 Hz |
| Breaking capacity | 100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2; 50 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ics] rated service short-circuit breaking capacity | 100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2; 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 |
| Control type | Rotary handle |
| [In] rated current | 65 A |
| Thermal protection adjustment range | 48 … 65 A conforming to IEC 60947-2 |
| Magnetic tripping current | 910 A |
| [Ith] conventional free air thermal current | 65 A conforming to IEC 60947-2 |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ui] rated insulation voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-2 |
| Phase failure sensitivity | Yes conforming to IEC 60947-4-1 |
| Suitability for isolation | Yes conforming to IEC 60947-1 |
| Dimensions (W x H x D) | 55 x 132 x 136 mm |
| Condition | New, original Schneider Electric |
Main characteristics
- Motor circuit breaker
- TeSys Deca frame 3
- 3P
- 48-65A
- thermal magnetic
- EverLink terminals
Typical applications
- Machine panels requiring a lockable isolator
- Pumps, fans and compressors
- Motor branches with rated current 48 … 65 A
- Replacement of a damaged GV3 breaker
Compatibility and replacement
Auxiliary contacts and other accessories for the GV3 are listed by Schneider in the data sheet; check the compatibility row before ordering accessories.
Frequently asked questions
What current range does it cover?
48 … 65 A, adjustable on the front dial.
Is the magnetic trip adjustable?
No. Only the thermal (overload) setting is adjustable; the magnetic trip is fixed at 910 A.
Is it the same as a GV2?
No. The GV3 is a larger frame for higher currents; GV2 and GV3 breakers are not interchangeable in the panel layout.
What is its breaking capacity?
Per Schneider: 50 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2.
How fast can you deliver, and is there a warranty?
Air shipping usually takes 5 to 7 days once the part is ready, to almost any country. Each part is new and original with a 1-year warranty. Message us on WhatsApp with the order number for a quotation.
Before you order
Compare the complete order number on the old unit with this page, including the suffix: in most ranges the last characters set the coil voltage, current range or version. If the label is worn, send us a photo and we will identify the part.
Need it fast? Send the order number, quantity and delivery country on WhatsApp or through the inquiry form and we reply with a quotation the same working day. All parts are new and original, covered by a 1-year warranty, and ship worldwide by air in 5 to 7 days once ready (shipping, payment and warranty). Local agents: Saudi Arabia, Iraq, the UAE, Egypt, Oman, Libya, Morocco, Mauritania, Yemen, Algeria and Jordan.