The Schneider Electric GV3P32 is a TeSys GV3 motor circuit breaker with thermal-magnetic protection, thermal setting 23 … 32 A, magnetic tripping at 448 A.
Set the thermal dial to the motor nameplate current. A breaker that trips at start-up can point to a wrong setting, a mechanical jam or a failing motor.
See our Schneider Electric range.
Technical data
| Schneider reference | GV3P32 |
|---|---|
| Product or component type | Motor circuit breaker |
| Device application | Motor protection |
| Trip unit technology | Thermal-magnetic |
| Poles description | 3P |
| Network type | AC |
| Utilisation category | Category A conforming to IEC 60947-2; AC-3 conforming to IEC 60947-4-1 |
| Network frequency | 50/60 Hz conforming to IEC 60947-2 |
| Motor power kW | 15 kW at 400/415 V AC 50/60 Hz; 18.5 kW at 500 V AC 50/60 Hz; 22 kW at 690 V AC 50/60 Hz |
| Breaking capacity | 100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2; 100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ics] rated service short-circuit breaking capacity | 100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2; 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 |
| Control type | Rotary handle |
| [In] rated current | 32 A |
| Thermal protection adjustment range | 23 … 32 A conforming to IEC 60947-2 |
| Magnetic tripping current | 448 A |
| [Ith] conventional free air thermal current | 32 A conforming to IEC 60947-2 |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ui] rated insulation voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-2 |
| Phase failure sensitivity | Yes conforming to IEC 60947-4-1 |
| Suitability for isolation | Yes conforming to IEC 60947-1 |
| Dimensions (W x H x D) | 55 x 132 x 136 mm |
| Condition | New, original Schneider Electric |
Key characteristics (per Schneider)
- Motor circuit breaker
- TeSys Deca frame 3
- 3P
- 23-32A
- thermal magnetic
- EverLink terminals
Typical applications
- Fuseless motor starters with TeSys Deca LC1D contactors
- Motor branches with rated current 23 … 32 A
- Pumps, fans and compressors
- Machine panels requiring a lockable isolator
Compatibility and replacement
Auxiliary contacts and other accessories for the GV3 are listed by Schneider in the data sheet; check the compatibility row before ordering accessories.
Frequently asked questions
Is it the same as a GV2?
No. The GV3 is a larger frame for higher currents; GV2 and GV3 breakers are not interchangeable in the panel layout.
What is its breaking capacity?
Per Schneider: 100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2.
What current range does it cover?
23 … 32 A, adjustable on the front dial.
Is the magnetic trip adjustable?
No. Only the thermal (overload) setting is adjustable; the magnetic trip is fixed at 448 A.
Do you ship to my country, and what is the warranty?
Yes. RendatSP ships worldwide from Yiwu, China, by air in 5 to 7 days once the part is ready, and every part carries a 1-year warranty. Send the order number and quantity on WhatsApp and we will reply with a quotation.
How to order
Message us the order number and quantity. For breakdowns, tell us the delivery address and we will offer the fastest shipping option. If the exact part is discontinued, we confirm the official successor before quoting.
Every part RendatSP supplies is new and original, carries a 1-year warranty and ships worldwide by air in 5 to 7 days once ready (shipping, payment and warranty). Send us the order number and quantity on WhatsApp or through the inquiry form and we will quote the same working day. Agents in Saudi Arabia, Iraq, the UAE, Egypt, Oman, Libya, Morocco, Mauritania, Yemen, Algeria and Jordan.