Danfoss order code 060L111566 is a thermostat from the KP range: KP71 Thermostat -5 to 20 °C, Remote Bulb 2 m, Manual Reset.
KP thermostats are standard parts in cold rooms, display cases and HVAC systems; the replacement must match the temperature range, sensor type and capillary length of the old unit.
More Danfoss drives, sensors, switches and valves: Danfoss range.
Technical data
| Danfoss order code | 060L111566 |
|---|---|
| Net weight | 0.362 Kilogram |
| Type | KP71 |
| Ambient temperature range (°C) | -40 °C to 65 °C |
| Approval | BV CCC CE CMIM DNV EAC GL LR LVD RINA RoHS China c UL us UL873, CS C22.2 UA |
| Capillary tube length (mm) | 2000 mm |
| Charge type | Adsorption |
| Contact function | SPDT |
| Contact rating | AC15=10 A, 400 V AC1=16 A, 400 V AC3=16 A, 400 V DC13=12 W, 220 V LR=112 A, 400 V |
| Differential at max. setting (°C) | 3 °C |
| Differential at min. setting (°C) | 3 °C |
| Differential type | Fixed |
| Electrical connection | Rubber cable gland |
| Electrical connection size | 6-14 mm |
| Electrical standard | EN 60947-5 |
| EN 60947 electrical properties | Insulation: 400V Pollution degree: 3 Rated impulse voltage: 4 kV Short circuit prot, fuse: 16A |
| Enclosure rating IP | IP30 |
| Enclosure rating Nema (~) | 1 |
| Maximum sensor temperature (°C) | 80 °C |
| Product description | Thermostat |
| Reset function | Manual Min |
| Sensor size (Ø x L) (mm) | 9.5 x 115 mm |
| Sensor type | Remote bulb |
| Temperature range (°C) | -5 °C to 20 °C |
| Brand | Danfoss |
| Condition | New, original |
Configuration and key data (per Danfoss)
- Temperature range (°C): -5 to 20
- Reset function: Manual Min
- Contact function: SPDT
- Sensor type: Remote bulb
- Capillary tube length (mm): 2000
- Enclosure rating IP: IP30
Typical applications
- Cold rooms and refrigerated cabinets
- Defrost and frost protection
- Heating and ventilation control
- Replacement of a failed thermostat
Compatibility and replacement
Order with the complete Danfoss code 060L111566; in Danfoss product codes the variant digits select the voltage, range, connection or option set, so a part with a different code may not be a direct replacement.
The values in the table come from the official Danfoss product data; if your old unit shows different values, send us a photo of its label and we will check it.
Before you replace it
- Temperature range and differential
- Reset function
- Sensor type and capillary length
Frequently asked questions
How is it connected electrically?
Rubber cable gland, according to the Danfoss product data.
What contact does it have?
SPDT, according to the Danfoss product data.
What can the contact switch?
AC15=10 A, 400 V AC1=16 A, 400 V AC3=16 A, 400 V DC13=12 W, 220 V LR=112 A, 400 V, according to the Danfoss product data.
What is the protection rating?
IP30, according to the Danfoss product data.
What temperature range does it cover?
-5 °C to 20 °C, according to the Danfoss product data.
Is it new and original?
Yes. We supply new, original parts in the manufacturer packaging, with a 1-year warranty.
How fast can you deliver, and is there a warranty?
Air shipping usually takes 5 to 7 days once the part is ready, to almost any country. Each part is new and original with a 1-year warranty. Message us on WhatsApp with the order number for a quotation.
Before you order
Compare the complete order number on the old unit with this page, including the suffix: in most ranges the last characters set the coil voltage, current range or version. If the label is worn, send us a photo and we will identify the part.
Need it fast? Send the order number, quantity and delivery country on WhatsApp or through the inquiry form and we reply with a quotation the same working day. All parts are new and original, covered by a 1-year warranty, and ship worldwide by air in 5 to 7 days once ready (shipping, payment and warranty). Local agents: Saudi Arabia, Iraq, the UAE, Egypt, Oman, Libya, Morocco, Mauritania, Yemen, Algeria and Jordan.