Genuine ABB TF42-1.7, order code 1SAZ721201R1028: Thermal Overload Relay 1.3-1.7 A, Class 10, 1NO+1NC.
Thermal overload relays are standard parts of every direct-on-line and star-delta starter; a relay that trips repeatedly or no longer resets is replaced with the same type and current range.
More ABB contactors, overload relays and control parts: ABB range.
Technical data
| ABB type | TF42-1.7 |
|---|---|
| ABB order code | 1SAZ721201R1028 |
| Product Name | Thermal Overload Relay |
| Rated Operational Current AC-3 | 1.7 A |
| Number of Auxiliary Contacts NO | 1 |
| Number of Auxiliary Contacts NC | 1 |
| Setting Range | 1.3 … 1.7 A |
| Rated Operational Current | 1.7 A |
| Trip Class | class 10 |
| Rated Operational Voltage | Auxiliary Circuit 600 V AC / DC Main Circuit 690 V AC |
| Rated Insulation Voltage | 690 V |
| Rated Impulse Withstand Voltage | Auxiliary Circuit 6 kV Main Circuit 6 kV |
| Number of Poles | 3 |
| Number of Protected Poles | 3 |
| Suitable For | AF09 AF12 AF16 AF26 AF30 AF38 |
| Conventional Free-air Thermal Current | Auxiliary Circuit NC 6 A Auxiliary Circuit NO 4 A |
| Rated Frequency | Auxiliary Circuit 50 Hz Auxiliary Circuit 60 Hz Auxiliary Circuit DC Main Circuit 50Hz Main Circuit 60 Hz |
| Degree of Protection | IP20 |
| Wire Stripping Length | Auxiliary Circuit 9 mm Main Circuit 12 mm |
| Tightening Torque | Auxiliary Circuit 1 … 1.5 N·m Main Circuit 1.5 … 2.5 N·m |
| Mounting Position | Position 1 to 5 |
| Power Loss | at Rated Operating Conditions per Pole 1.1 … 2.0 W |
Main data, as listed by ABB
- Setting Range: 1.3 … 1.7 A
- Trip Class: class 10
- Suitable For: AF09 AF12 AF16 AF26 AF30 AF38
- Rated Operational Current AC-3: 1.7 A
- Ambient Air Temperature Compensation: Yes
Typical applications
- Replacement of a failed overload relay
- Conveyors and machine motors
- Pumps, fans and compressors
- Direct-on-line motor starters with AF contactors
- Star-delta starters
Compatibility and replacement
Order with the full type TF42-1.7 or the order code 1SAZ721201R1028; in ABB type designations the last digits select the current range or the coil voltage, so a part with a different suffix is not always a drop-in replacement.
If the old label is worn, send us a photo and we will confirm the matching ABB type before quoting.
Replacement checklist
- Contactor size it mounts on
- Setting range versus the motor full-load current
- Trip class
Frequently asked questions
What ambient temperature is allowed?
Operation -25 … +60 °C Operation Compensated -25 … +60 °C Storage -50 … +80 °C, according to ABB’s product data.
What is the AC-3 rating?
1.7 A, according to ABB’s product data.
Which standards does it meet?
IEC/EN 60947-1 IEC/EN 60947-4-1 IEC/EN 60947-5-1 UL 60947-1 UL 60947-4-1, according to ABB’s product data.
Can I get the datasheet?
The official manufacturer data is the source of the technical values above; we can send the datasheet with the quotation on request.
Do you ship to my country, and what is the warranty?
Yes. RendatSP ships worldwide from Yiwu, China, by air in 5 to 7 days once the part is ready, and every part carries a 1-year warranty. Send the order number and quantity on WhatsApp and we will reply with a quotation.
Before you order
Compare the complete order number on the old unit with this page, including the suffix: in most ranges the last characters set the coil voltage, current range or version. If the label is worn, send us a photo and we will identify the part.
Every part RendatSP supplies is new and original, carries a 1-year warranty and ships worldwide by air in 5 to 7 days once ready (shipping, payment and warranty). Send us the order number and quantity on WhatsApp or through the inquiry form and we will quote the same working day. Agents in Saudi Arabia, Iraq, the UAE, Egypt, Oman, Libya, Morocco, Mauritania, Yemen, Algeria and Jordan.