The ABB S202-D16 (order code 2CDS252001R0161) is a two-pole miniature circuit breaker from the System pro M compact S200 range, rated 16 A with a D tripping characteristic. Like every S200, it is current-limiting and combines a delayed thermal release for overloads with an electromagnetic release that trips instantly at 10 to 20 x In for short circuits.
Reading the type code: S202 = S200 series, 2 protected poles; D = tripping curve; 16 = rated current in amperes. The breaker is 2 modules wide (35 mm) and snaps onto a 35 mm DIN rail.
Technical data
| ABB type | S202-D16 |
|---|---|
| ABB order code | 2CDS252001R0161 |
| Range | System pro M compact S200 |
| Poles | 2P |
| Tripping characteristic | D |
| Rated current (In) | 16 A |
| Rated operational voltage Un (IEC/EN 60898-1) | 400 V AC |
| Rated operational voltage Ue (IEC/EN 60947-2) | 440 V AC |
| Rated short-circuit capacity Icn (IEC/EN 60898-1) | 6 kA |
| Ultimate breaking capacity Icu (IEC/EN 60947-2) | 10 kA |
| Service breaking capacity Ics (IEC/EN 60947-2) | 7.5 kA |
| Instantaneous (magnetic) trip range | 10 to 20 x In |
| Thermal release | 1.13 x In no trip (> 1 h), 1.45 x In trip (< 1 h); reference 30 °C |
| Rated insulation voltage Ui | 250 V AC phase-earth, 500 V AC phase-phase |
| Rated impulse withstand voltage Uimp | 4 kV |
| Electrical endurance | 20,000 operations (AC) |
| Mechanical endurance | 20,000 operations |
| Terminals | Failsafe bi-directional cylinder-lift, 35 mm² solid/stranded, 25 mm² flexible, busbar 10 mm² |
| Tightening torque | 2.8 N·m (Pozidriv 2) |
| Dimensions per pole (H x D x W) | 88 x 69 x 17.5 mm |
| Width | 35 mm (2 modules) |
| Protection degree | IP20 (IP40 in enclosure with cover) |
| Ambient temperature | -25 to +55 °C |
| Standards | IEC/EN 60898-1, IEC/EN 60947-2, UL 1077 |
| Condition | New, original ABB |
Typical applications
- Transformer primaries and control transformers
- Pumps and compressors started direct-on-line
- Industrial distribution boards feeding machinery
- Heaters and lamp groups with large switch-on current
- Direct replacement of an ABB S202-D16 with the same order code
Compatibility and replacement
The order code 2CDS252001R0161 identifies exactly this pole count, curve and rating. Bottom-fitting auxiliary and signal contacts, shunt trips, undervoltage releases and motor operating devices from the System pro M compact range fit the S200 (accessories are sold separately). If your installation needs 10 kA breaking capacity, the S200 M version of the same rating has the same 88 x 69 mm pole size. When replacing, keep the curve (D) and rating (16 A) the circuit was designed for.
Frequently asked questions
Should I use the D curve or the C curve?
The D curve trips instantly at 10 to 20 x In; the C curve trips at 5 to 10 x In. D is for loads with heavy inrush such as motors and transformers; for ordinary circuits C trips magnetically at a lower fault current.
How many operations will it last?
ABB rates S200 breakers of 16 A at 20,000 operations (AC) electrically and 20,000 operations mechanically.
Can it be fed from the bottom?
Yes. ABB lists the supply direction as optional and the mounting position as any, and the twin terminals accept cable and busbar together.
Related parts
- ABB S202-D20 Miniature Circuit Breaker 2P 20A D-Curve
- ABB S202-D25 Miniature Circuit Breaker 2P 25A D-Curve
- ABB S204-D16 Miniature Circuit Breaker 4P 16A D-Curve
- All ABB Miniature Circuit Breakers
Used across industrial control panels, distribution boards and machine-building applications for reliable overcurrent and short-circuit protection.
Every part RendatSP supplies is new and original, carries a 1-year warranty and ships worldwide by air in 5 to 7 days once ready (shipping, payment and warranty). Send us the part number and quantity on WhatsApp or through the inquiry form and we will quote the same working day. Agents in Saudi Arabia, Iraq, the UAE, Egypt, Oman, Libya, Morocco, Mauritania, Yemen, Algeria and Jordan.