The ABB S202-C16 (order code 2CDS252001R0164) is a two-pole miniature circuit breaker from the System pro M compact S200 range, rated 16 A with a C tripping characteristic. Like every S200, it is current-limiting and combines a delayed thermal release for overloads with an electromagnetic release that trips instantly at 5 to 10 x In for short circuits.
Reading the type code: S202 = S200 series, 2 protected poles; C = tripping curve; 16 = rated current in amperes. The breaker is 2 modules wide (35 mm) and snaps onto a 35 mm DIN rail.
Technical data
| ABB type | S202-C16 |
|---|---|
| ABB order code | 2CDS252001R0164 |
| Range | System pro M compact S200 |
| Poles | 2P |
| Tripping characteristic | C |
| Rated current (In) | 16 A |
| Rated operational voltage Un (IEC/EN 60898-1) | 400 V AC |
| Rated operational voltage Ue (IEC/EN 60947-2) | 440 V AC |
| Rated short-circuit capacity Icn (IEC/EN 60898-1) | 6 kA |
| Ultimate breaking capacity Icu (IEC/EN 60947-2) | 10 kA |
| Service breaking capacity Ics (IEC/EN 60947-2) | 7.5 kA |
| Instantaneous (magnetic) trip range | 5 to 10 x In |
| Thermal release | 1.13 x In no trip (> 1 h), 1.45 x In trip (< 1 h); reference 30 °C |
| Energy limiting class | 3 |
| Rated insulation voltage Ui | 250 V AC phase-earth, 500 V AC phase-phase |
| Rated impulse withstand voltage Uimp | 4 kV |
| Electrical endurance | 20,000 operations (AC) |
| Mechanical endurance | 20,000 operations |
| Terminals | Failsafe bi-directional cylinder-lift, 35 mm² solid/stranded, 25 mm² flexible, busbar 10 mm² |
| Tightening torque | 2.8 N·m (Pozidriv 2) |
| Dimensions per pole (H x D x W) | 88 x 69 x 17.5 mm |
| Width | 35 mm (2 modules) |
| Protection degree | IP20 (IP40 in enclosure with cover) |
| Ambient temperature | -25 to +55 °C |
| Standards | IEC/EN 60898-1, IEC/EN 60947-2, UL 1077 |
| Condition | New, original ABB |
Typical applications
- Lighting and socket-outlet final circuits
- Small motors and fans with moderate inrush
- Resistive heating loads
- Distribution boards in commercial buildings
- Direct replacement of an ABB S202-C16 with the same order code
Compatibility and replacement
The order code 2CDS252001R0164 identifies exactly this pole count, curve and rating. Bottom-fitting auxiliary and signal contacts, shunt trips, undervoltage releases and motor operating devices from the System pro M compact range fit the S200 (accessories are sold separately). If your installation needs 10 kA breaking capacity, the S200 M version of the same rating has the same 88 x 69 mm pole size. When replacing, keep the curve (C) and rating (16 A) the circuit was designed for.
Frequently asked questions
Should I use the C curve or the D curve?
The C curve trips instantly at 5 to 10 x In; the D curve trips at 10 to 20 x In. Use C for general circuits; move to D only for loads with heavy inrush such as motors or transformers.
Can it be fed from the bottom?
Yes. ABB lists the supply direction as optional and the mounting position as any, and the twin terminals accept cable and busbar together.
Does high ambient temperature affect it?
Yes. Per ABB, the thermal release is calibrated at 30 °C and the tripping current falls by about 6 % for every 10 K above that, so allow for it in hot panels.
Related parts
- ABB S202-C20 Miniature Circuit Breaker 2P 20A C-Curve
- ABB S202-C10 Miniature Circuit Breaker 2P 10A C-Curve
- ABB S204-C16 Miniature Circuit Breaker 4P 16A C-Curve
- All ABB Miniature Circuit Breakers
Used across industrial control panels, distribution boards and machine-building applications for reliable overcurrent and short-circuit protection.
Every part RendatSP supplies is new and original, carries a 1-year warranty and ships worldwide by air in 5 to 7 days once ready (shipping, payment and warranty). Send us the part number and quantity on WhatsApp or through the inquiry form and we will quote the same working day. Agents in Saudi Arabia, Iraq, the UAE, Egypt, Oman, Libya, Morocco, Mauritania, Yemen, Algeria and Jordan.