The Schneider Electric LC1D32M7 is a TeSys Deca 3-pole contactor (3 NO main poles) rated 32 A in AC-3 up to 440 V, with a 220 V AC 50/60 Hz coil. Per the Schneider data sheet it switches a motor of 15 kW at 380/400 V AC-3, and it has a built-in 1 NO + 1 NC auxiliary contact and screw clamp terminals.
Decode the reference: LC1D = TeSys D contactor, 32 = 32 A AC-3 rating, M7 = 220 V AC 50/60 Hz coil. TeSys D contactors are among the most common parts in motor starters, pump panels, compressor panels and machine control cabinets worldwide, which is why a stock of spares saves long stops.
For larger ratings see the TeSys D LC1D 115 A to 620 A contactors, or browse all Schneider parts.
Technical data
| Schneider reference | LC1D32M7 |
|---|---|
| Range | TeSys Deca Advanced |
| Poles | 3P (3 NO) |
| Utilisation category | AC-3; AC-3e; AC-1; AC-4 |
| Rated operational current [Ie] | 32 A (at <60 °C) at <= 440 V AC AC-3 for power circuit; 50 A (at <60 °C) at <= 440 V AC AC-1 for power circuit; 32 A (at <60 °C) at <= 440 V AC AC-3e for power circuit |
| Rated operational voltage [Ue] | Power circuit: <= 690 V AC 25…400 Hz; Power circuit: <= 300 V DC |
| Coil voltage [Uc] | 220 V AC 50/60 Hz |
| Motor power (AC-3) | 7.5 kW at 220/230 V AC 50/60 Hz (AC-3); 15 kW at 380/400 V AC 50/60 Hz (AC-3); 15 kW at 415/440 V AC 50/60 Hz (AC-3); 18.5 kW at 500 V AC 50/60 Hz (AC-3); 18.5 kW at 660/690 V AC 50/60 Hz (AC-3) |
| Conventional thermal current [Ith] | 10 A (at 60 °C) for signalling circuit; 50 A (at 60 °C) for power circuit |
| Auxiliary contacts | 1 NO + 1 NC |
| Coil inrush / hold-in | 70 VA 60 Hz cos phi 0.75 (at 20 °C) / 7.5 VA 60 Hz cos phi 0.3 (at 20 °C) |
| Operating time | 12…22 ms closing; 4…19 ms opening |
| Mechanical durability | 15 Mcycles |
| Mounting | Plate; Rail |
| Degree of protection | IP20 front face conforming to IEC 60529 |
| Ambient temperature | -40…60 °C; 60…70 °C with derating |
| Dimensions (W x H x D) | 45 x 85 x 92 mm |
| Net weight | 0.375 kg |
| Product life status | Commercialised |
| Condition | New, original Schneider Electric |
Typical applications
- Direct-on-line and star-delta motor starters
- Pump, fan and compressor control panels
- Heating and resistive loads (AC-1)
- Machine control cabinets
Compatibility and replacement
The same frame is available with other coil voltages (the last letters of the reference change, for example M7 = 220 V AC, BD = 24 V DC). Make sure the coil voltage matches your control circuit. A TeSys LRD thermal overload relay mounts directly under the contactor for motor protection; choose the relay range by the motor full-load current. In our new range, Schneider lists LRD10, LRD14, LRD16, LRD21, LRD22 as compatible with LC1D32 (plain-text references).
Frequently asked questions
What does the M7 / BD at the end mean?
It is the coil code. M7 = 220 V AC 50/60 Hz, BD = 24 V DC. The power rating is the same; only the coil changes.
What motor size can it switch?
Per Schneider, 15 kW at 380/400 V in AC-3 duty. Ratings at other voltages are in the table.
Do you ship to my country, and what is the warranty?
Yes. RendatSP ships worldwide from Yiwu, China, by air in 5 to 7 days once the part is ready, and every part carries a 1-year warranty. Send the order number and quantity on WhatsApp and we will reply with a quotation.
Every part RendatSP supplies is new and original, carries a 1-year warranty and ships worldwide by air in 5 to 7 days once ready (shipping, payment and warranty). Send us the order number and quantity on WhatsApp or through the inquiry form and we will quote the same working day. Agents in Saudi Arabia, Iraq, the UAE, Egypt, Oman, Libya, Morocco, Mauritania, Yemen, Algeria and Jordan.