The Schneider Electric LC1D18BL is a TeSys Deca 3-pole contactor rated 18 A in AC-3 at up to 440 V, for motors of 7.5 kW at 380/400 V, with a 24 V DC coil. It carries 1 NO + 1 NC auxiliary contacts as standard. At 220/230 V the AC-3 motor rating is 4 kW.
TeSys D (now TeSys Deca) is probably the most widely installed contactor range in the world, so the LC1D is a standard spare in factories from the Gulf to North Africa. The coil letter code at the end of the reference sets the control voltage.
See our Schneider Electric range for TeSys overload relays and GV2 breakers.
Technical data
| Schneider reference | LC1D18BL |
|---|---|
| Product or component type | Contactor |
| Contactor application | Motor control; Resistive load |
| Utilisation category | AC-3; AC-3e; AC-1; AC-4 |
| Poles description | 3P |
| [Ue] rated operational voltage | Power circuit: <= 690 V AC 25…400 Hz; Power circuit: <= 300 V DC |
| [Ie] rated operational current | 18 A (at <60 °C) at <= 440 V AC AC-3 for power circuit; 32 A (at <60 °C) at <= 440 V AC AC-1 for power circuit; 18 A (at <60 °C) at <= 440 V AC AC-3e for power circuit |
| [Uc] control circuit voltage | 24 فولت DC |
| Motor power kW | 4 kW at 220/230 V AC 50/60 Hz (AC-3); 7.5 kW at 380/400 V AC 50/60 Hz (AC-3); 9 kW at 415/440 V AC 50/60 Hz (AC-3); 10 kW at 500 V AC 50/60 Hz (AC-3) |
| Motor power hp | 1 hp at 115 V AC 50/60 Hz for 1 phase motors; 3 hp at 230/240 V AC 50/60 Hz for 1 phase motors; 5 hp at 200/208 V AC 50/60 Hz for 3 phases motors |
| Compatibility code | LC1D |
| Pole contact composition | 3 NO |
| Protective cover | With |
| [Ith] conventional free air thermal current | 10 A (at 60 °C) for signalling circuit; 32 A (at 60 °C) for power circuit |
| Irms rated making capacity | 140 A AC for signalling circuit conforming to IEC 60947-5-1; 250 A DC for signalling circuit conforming to IEC 60947-5-1 |
| Dimensions (W x H x D) | 45 x 77 x 95 mm |
| Condition | New, original Schneider Electric |
Key characteristics (per Schneider)
- Contactor
- TeSys Deca
- 3P(3NO)
- AC-3/3e
- <=440V
- 18A
- 24V DC low consumption coil
- screw clamp terminals
Typical applications
- Motor starters up to 7.5 kW at 400 V
- Heating and resistive loads (AC-1)
- Pump, fan and compressor panels
- Star-delta starter assemblies
Compatibility and replacement
Pairs with the TeSys LRD thermal overload relay (direct mounting) and the GV2 motor circuit breaker. Add-on blocks such as LADN11 (1NO+1NC) or LADN22 (2NO+2NC) fit on the front. LC1D contactors from older TeSys D production are replaced one-to-one by TeSys Deca of the same reference.
Frequently asked questions
How fast does it close and open?
Per Schneider: 77 ±15 % ms closing; 25 ±20 % ms opening.
How long does it last mechanically?
Schneider gives a mechanical durability of 30 Mcycles.
What motor size can it switch?
Up to 7.5 kW at 380/400 V in AC-3 (18 A).
Can I add auxiliary contacts?
Yes, front-mounted LADN blocks and side-mounted LAD8 blocks can be added.
Do you ship to my country, and what is the warranty?
Yes. RendatSP ships worldwide from Yiwu, China, by air in 5 to 7 days once the part is ready, and every part carries a 1-year warranty. Send the order number and quantity on WhatsApp and we will reply with a quotation.
Before you order
Compare the complete order number on the old unit with this page, including the suffix: in most ranges the last characters set the coil voltage, current range or version. If the label is worn, send us a photo and we will identify the part.
Every part RendatSP supplies is new and original, carries a 1-year warranty and ships worldwide by air in 5 to 7 days once ready (shipping, payment and warranty). Send us the order number and quantity on WhatsApp or through the inquiry form and we will quote the same working day. Agents in Saudi Arabia, Iraq, the UAE, Egypt, Oman, Libya, Morocco, Mauritania, Yemen, Algeria and Jordan.