Rated 32A with 3P, the Schneider A9F75332 belongs to the Acti9 iC60N family of modular circuit breakers, one of the most common breaker ranges in industrial and building panels.
A miniature circuit breaker protects the cable behind it: the thermal element trips on sustained overload and the magnetic element trips almost instantly on a short circuit. After the fault is cleared the breaker is simply switched back on.
See our Schneider Electric range.
Technical data
| Schneider reference | A9F75332 |
|---|---|
| Product or component type | Miniature circuit-breaker |
| Device application | Distribution |
| Poles description | 3P |
| Number of protected poles | 3 |
| [In] rated current | 32 A |
| Network type | AC; DC |
| Trip unit technology | Thermal-magnetic |
| Curve code | D |
| Product compatibility | Vigi iC60 single terminal add-on residual current device 40/63 A; Quick Vigi iC60 single terminal add-on residual current device 40 A |
| Utilisation category | Category A conforming to EN/IEC 60947-2 |
| Suitability for isolation | Yes conforming to EN/IEC 60898-1; Yes conforming to EN/IEC 60947-2 |
| Network frequency | 50/60 Hz |
| [Ue] rated operational voltage | 12…133 V AC 50/60 Hz; 220…240 V AC 50/60 Hz; 380…415 V AC 50/60 Hz; 440 V AC 50/60 Hz; <= 180 V DC |
| Magnetic tripping limit | 12 x In +/- 20 % |
| Breaking capacity | 36 kA Icu at 12…133 V AC 50/60 Hz conforming to EN/IEC 60947-2; 20 kA Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
| [Ics] rated service breaking capacity | 27 kA 75 % x Icu at 12…133 V AC 50/60 Hz conforming to EN/IEC 60947-2; 15 kA 75 % x Icu at 220…240 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
| Limitation class | 3 conforming to EN/IEC 60898-1 |
| [Ui] rated insulation voltage | 500 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
| Width | 54 mm |
| Tightening torque | 3.5 N.m top or bottom |
| Dimensions (W x H x D) | 54 x 85 x 78.5 mm |
| Condition | New, original Schneider Electric |
Key characteristics (per Schneider)
- Miniature circuit breaker (MCB)
- Acti9 iC60N
- 3P
- 32A
- D curve
- 6000A (IEC/EN 60898-1)
- 10kA (IEC/EN 60947-2)
Typical applications
- Protection of small motors, heaters and transformers
- Protection of control-circuit and auxiliary supplies
- Replacement of a damaged or worn breaker
- Lighting and socket circuits in plants and workshops
Compatibility and replacement
Match poles (3P), rated current (32A), curve (D) and breaking capacity when replacing. Schneider lists these compatible add-ons: Vigi iC60 single terminal add-on residual current device 40/63 A; Quick Vigi iC60 single terminal add-on residual current device 40 A.
Frequently asked questions
Which voltages is it rated for?
Per Schneider: 12…133 V AC 50/60 Hz; 220…240 V AC 50/60 Hz; 380…415 V AC 50/60 Hz; 440 V AC 50/60 Hz; <= 180 V DC.
What is its breaking capacity?
Per Schneider: 6000 A Icn at 400 V AC 50/60 Hz; 20 kA Icu at 220…240 V AC 50/60 Hz.
How wide is it on the DIN rail?
54 mm per Schneider.
Can I add residual current protection?
Yes. Schneider lists Vigi iC60 single terminal add-on residual current device 40/63 A as a compatible add-on.
Can I get a price and delivery time?
Prices are quoted on request. Send the order number, quantity and delivery country on WhatsApp and we will reply with price and delivery time; air shipping is usually 5 to 7 days once ready, with a 1-year warranty.
How to order
Message us the order number and quantity. For breakdowns, tell us the delivery address and we will offer the fastest shipping option. If the exact part is discontinued, we confirm the official successor before quoting.
RendatSP ships from Yiwu, China, to factories worldwide; air delivery usually takes 5 to 7 days once the part is ready. The part is new and original with a 1-year warranty (shipping, payment and warranty). For a quotation, message us on WhatsApp with the order number and quantity. We also have agents in Saudi Arabia, Iraq, the UAE, Egypt, Oman, Libya, Morocco, Mauritania, Yemen, Algeria and Jordan.