Schneider A9F74150: 1P 50A Acti9 iC60N MCB with a curve C thermal-magnetic trip unit and a breaking capacity of 6000 A Icn at 230 V AC 50/60 Hz.
When a breaker of this type trips repeatedly, check the load first; if the breaker itself is damaged or no longer latches, replace it with the same pole number, rating (50A) and curve (C).
See our Schneider Electric range.
Technical data
| Schneider reference | A9F74150 |
|---|---|
| Product or component type | Miniature circuit-breaker |
| Device application | Distribution |
| Poles description | 1P |
| Number of protected poles | 1 |
| [In] rated current | 50 A |
| Network type | DC; AC |
| Trip unit technology | Thermal-magnetic |
| Curve code | C |
| Product compatibility | Vigi iC60 single terminal add-on residual current device 63 A |
| Utilisation category | Category A conforming to EN/IEC 60947-2 |
| Suitability for isolation | Yes conforming to EN/IEC 60898-1; Yes conforming to EN/IEC 60947-2 |
| Network frequency | 50/60 Hz |
| [Ue] rated operational voltage | 12…60 V AC 50/60 Hz; 100…133 V AC 50/60 Hz; 220…240 V AC 50/60 Hz; 12…60 V DC; 60…72 V DC |
| Magnetic tripping limit | 8 x In +/- 20 % |
| Breaking capacity | 36 kA Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2; 20 kA Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
| [Ics] rated service breaking capacity | 27 kA 75 % x Icu at 12…60 V AC 50/60 Hz conforming to EN/IEC 60947-2; 15 kA 75 % x Icu at 100…133 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
| Limitation class | 3 conforming to EN/IEC 60898-1 |
| [Ui] rated insulation voltage | 500 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
| Width | 18 مم |
| Tightening torque | 3.5 N.m top or bottom |
| Dimensions (W x H x D) | 18 x 85 x 78.5 mm |
| Condition | New, original Schneider Electric |
Key characteristics (per Schneider)
- Miniature circuit breaker (MCB)
- Acti9 iC60N
- 1P
- 50A
- C curve
- 6000A (IEC/EN 60898-1)
- 10kA (IEC/EN 60947-2)
Typical applications
- Lighting and socket circuits in plants and workshops
- Replacement of a damaged or worn breaker
- Protection of control-circuit and auxiliary supplies
- Outgoing feeders in distribution boards
Compatibility and replacement
Match poles (1P), rated current (50A), curve (C) and breaking capacity when replacing. Schneider lists these compatible add-ons: Vigi iC60 single terminal add-on residual current device 63 A.
Frequently asked questions
What is its breaking capacity?
Per Schneider: 6000 A Icn at 230 V AC 50/60 Hz; 10 kA Icu at 220…240 V AC 50/60 Hz.
Which tripping curve does it have?
Curve C; Schneider gives the magnetic tripping limit as 8 x In +/- 20 %.
Which voltages is it rated for?
Per Schneider: 12…60 V AC 50/60 Hz; 100…133 V AC 50/60 Hz; 220…240 V AC 50/60 Hz; 12…60 V DC; 60…72 V DC.
How wide is it on the DIN rail?
18 mm per Schneider.
Do you ship to my country, and what is the warranty?
Yes. RendatSP ships worldwide from Yiwu, China, by air in 5 to 7 days once the part is ready, and every part carries a 1-year warranty. Send the order number and quantity on WhatsApp and we will reply with a quotation.
Before you order
Compare the complete order number on the old unit with this page, including the suffix: in most ranges the last characters set the coil voltage, current range or version. If the label is worn, send us a photo and we will identify the part.
Every part RendatSP supplies is new and original, carries a 1-year warranty and ships worldwide by air in 5 to 7 days once ready (shipping, payment and warranty). Send us the order number and quantity on WhatsApp or through the inquiry form and we will quote the same working day. Agents in Saudi Arabia, Iraq, the UAE, Egypt, Oman, Libya, Morocco, Mauritania, Yemen, Algeria and Jordan.