The Inovance GL20-4DA-INT is a GL20 I/O module – 4-channel analog output module, 16-bit.
Slim I/O modules like the GL20 range save about two thirds of the cabinet space of the previous GL10 generation and use tool-free spring terminals for quick replacement.
More Inovance PLCs and I/O modules: Inovance range.
The ratings in the table are taken from the official Inovance GL20 I/O module brochure (inovance.eu).
Technical data
| Model | GL20-4DA-INT |
|---|---|
| Material code | 01440741 |
| الوصف | 4-channel analog output module, 16-bit |
| Outputs | 4, voltage/current |
| Resolution | 16-bit |
| Conversion time | 60 us/channel |
| Voltage ranges | ±10 V, 0-10 V, ±5 V, 0-5 V, 1-5 V (load 1 kΩ) |
| Current ranges | 0-20 mA, 4-20 mA (load 0 to 600 Ω) |
| Accuracy (25 °C) | ±0.1% (full range) |
| Diagnostics | Open-circuit detection and over-temperature protection |
| Width | 12 mm |
| IP rating | IP20 |
| Certification | CE & UL |
| Ambient temperature | -20 to +55 °C |
| Brand | Inovance |
| Condition | New, original |
Main features
- Colour code for each module type
- Microsecond-level response and synchronous control
- Tool-free spring terminals with 1.5 mm² apertures
- Removable terminals
Typical applications
- Replacement of a failed module
- Packaging and assembly machines
- Machine I/O expansion of Easy PLCs
- Process signals in small plants
- Remote I/O stations over EtherCAT, PROFINET or EtherNet/IP
Compatibility and replacement
Order with the complete model GL20-4DA-INT: GL20 codes give the channel count and signal type (END = digital input, ETP/ETN = PNP/NPN transistor output, ER = relay, AD/DA = analog, PT/TC = temperature), and -INT marks the international version.
Check the label of the old module – modules of the same width can carry different signal types.
What to check first
- CPU model and firmware of the old PLC
- Communication ports used (RS485, CAN, Ethernet, EtherCAT)
- Expansion modules and cards fitted
Frequently asked questions
What is the current ranges?
0-20 mA, 4-20 mA (load 0 to 600 Ω), according to Inovance.
What is the voltage ranges?
±10 V, 0-10 V, ±5 V, 0-5 V, 1-5 V (load 1 kΩ), according to Inovance.
What is the resolution?
16-bit, according to Inovance.
Which controllers can use it?
Easy and AM300/AM500 PLCs as local expansion, and AC700, AC800, H5U and AM controllers through GL20 bus couplers (remote).
What is the conversion time?
60 us/channel, according to Inovance.
What does this module do?
4-channel analog output module, 16-bit, according to Inovance.
Do you supply larger quantities for projects?
Yes. For panel builders, OEMs and plant projects we quote complete lists; send the bill of materials on WhatsApp or through the inquiry form.
Can I get a price and delivery time?
Prices are quoted on request. Send the order number, quantity and delivery country on WhatsApp and we will reply with price and delivery time; air shipping is usually 5 to 7 days once ready, with a 1-year warranty.
How to order
Message us the order number and quantity. For breakdowns, tell us the delivery address and we will offer the fastest shipping option. If the exact part is discontinued, we confirm the official successor before quoting.
Need it fast? Send the order number, quantity and delivery country on WhatsApp or through the inquiry form and we reply with a quotation the same working day. All parts are new and original, covered by a 1-year warranty, and ship worldwide by air in 5 to 7 days once ready (shipping, payment and warranty). Local agents: Saudi Arabia, Iraq, the UAE, Egypt, Oman, Libya, Morocco, Mauritania, Yemen, Algeria and Jordan.