Genuine ABB TF65-67, order code 1SAZ811201R1007: Thermal Overload Relay 57-67 A, Class 10, 1NO+1NC.
The TF range is the overload relay series designed for ABB AF contactors; the setting dial covers a current band, so the replacement must have the band that contains the motor full-load current.
More ABB contactors, overload relays and control parts: ABB range.
Technical data
| ABB type | TF65-67 |
|---|---|
| ABB order code | 1SAZ811201R1007 |
| Product Name | Thermal Overload Relay |
| Rated Operational Current AC-3 | 67 A |
| Number of Auxiliary Contacts NO | 1 |
| Number of Auxiliary Contacts NC | 1 |
| Setting Range | 57 … 67 A |
| Rated Operational Current | 67 A |
| Trip Class | class 10 |
| Rated Operational Voltage | Auxiliary Circuit 600 V AC / DC Main Circuit 690/440 V AC/V DC |
| Rated Insulation Voltage | 690 V |
| Rated Impulse Withstand Voltage | Auxiliary Circuit 6 kV Main Circuit 8 kV |
| Number of Poles | 3 |
| Number of Protected Poles | 3 |
| Suitable For | AF40 AF52 AF65 |
| Conventional Free-air Thermal Current | Auxiliary Circuit NC 6 A Auxiliary Circuit NO 4 A |
| Rated Frequency | Auxiliary Circuit 50 Hz Auxiliary Circuit 60 Hz Auxiliary Circuit DC Main Circuit 50Hz Main Circuit 60 Hz |
| Degree of Protection | Housing IP20 Main Circuit Terminals IP10 |
| Wire Stripping Length | Auxiliary Circuit 9 mm Main Circuit 17 mm |
| Tightening Torque | Auxiliary Circuit 1 … 1.2 N·m Main Circuit 4.0 … 4.5 N·m |
| Mounting Position | Position 1 to 6 |
| Power Loss | at Rated Operating Conditions per Pole 2.5 … 3.4 W |
Main data, as listed by ABB
- Setting Range: 57 … 67 A
- Trip Class: class 10
- Suitable For: AF40 AF52 AF65
- Rated Operational Current AC-3: 67 A
- Ambient Air Temperature Compensation: Yes
Typical applications
- Pumps, fans and compressors
- Conveyors and machine motors
- Replacement of a failed overload relay
- Direct-on-line motor starters with AF contactors
- Star-delta starters
Compatibility and replacement
Order with the full type TF65-67 or the order code 1SAZ811201R1007; in ABB type designations the last digits select the current range or the coil voltage, so a part with a different suffix is not always a drop-in replacement.
If the old label is worn, send us a photo and we will confirm the matching ABB type before quoting.
Replacement checklist
- Reset mode (manual/automatic)
- Setting range versus the motor full-load current
- Contactor size it mounts on
Frequently asked questions
What is the setting range?
57 … 67 A, according to ABB’s product data.
What is the protection rating?
Housing IP20 Main Circuit Terminals IP10, according to ABB’s product data.
What trip class does it have?
Class 10, according to ABB’s product data.
Can I get the datasheet?
The official manufacturer data is the source of the technical values above; we can send the datasheet with the quotation on request.
Do you ship to my country, and what is the warranty?
Yes. RendatSP ships worldwide from Yiwu, China, by air in 5 to 7 days once the part is ready, and every part carries a 1-year warranty. Send the order number and quantity on WhatsApp and we will reply with a quotation.
Ordering tips
Send us the full order number from the label of the old part, or a clear photo of the label, together with the quantity you need. We check the number against the current manufacturer data before we quote and tell you if there is a newer replacement.
RendatSP ships from Yiwu, China, to factories worldwide; air delivery usually takes 5 to 7 days once the part is ready. The part is new and original with a 1-year warranty (shipping, payment and warranty). For a quotation, message us on WhatsApp with the order number and quantity. We also have agents in Saudi Arabia, Iraq, the UAE, Egypt, Oman, Libya, Morocco, Mauritania, Yemen, Algeria and Jordan.